刚芯管(CFRTP)PP100规范设计
一、管材选择
输送介质不同温度下许用压力见表1
![]()
![]()
表1 刚芯管(CFRTP)PP100在不同温度下许用工作压
S1.0 |
S1.6 |
S2.0 |
S2.5 |
S3.0 | |
130℃ | 0.4MPa | 0.6MPa | 0.8MPa | 1.6MPa | 2.0MPa |
95℃ | 0.6MPa | 0.8MPa | 1.0MPa | 1.6MPa | 2.5MPa |
70℃ | 0.8MPa | 1.0MPa | 1.6MPa | 2.0MPa | 2.5MPa |
60℃ | 1.0MPa | 1.6MPa | 2.0MPa | 2.5MPa | 3.0MPa |
二、产品规格
刚芯管PP100产品规格见表2
表2 刚芯管(CFRTP)PP100产品规格
公称直径 (DN) (mm) | 壁厚(mm) |
长度 | ||
1.0<PN≤2.0Mpa | 2.0<PN≤4.0Mpa | 4.0<PN≤6.0Mpa | ||
80 | ≥8.0 | ≥8.0 | ≥8.5 |
6-12M/根 |
100 | ≥8.5 | ≥8.5 | ≥9.0 | |
125 | ≥8.5 | ≥9.0 | ≥9.5 | |
150 | ≥9.0 | ≥9.5 | ≥10.0 | |
200 | ≥9.5 | ≥10.0 | ≥10.5 | |
250 | ≥9.8 | ≥10.5 | ≥11.0 | |
300 | ≥10.0 | ≥11.0 | ≥11.5 | |
350 | ≥10.5 | ≥11.5 | ≥12.0 | |
400 | ≥11.0 | ≥12.0 | ≥12.5 | |
450 | ≥11.5 | ≥12.5 | ≥13.0 | |
500 | ≥12.0 | ≥13.0 | ≥13.5 | |
600 | ≥12.5 | ≥13.5 | ≥14.0 | |
700 | ≥13.0 | ≥14.0 | ≥14.5 | |
800 | ≥14.0 | ≥14.5 | ≥15.0 | |
900 | ≥14.5 | ≥15.0 | ≥15.5 | |
1000 | ≥15.0 | ≥15.5 | ≥16.0 | |
1100 | ≥15.5 | ≥16.0 | ≥16.5 | |
1200 | ≥16.0 | ≥16.5 | ≥17.0 | |
刚芯管PP100工作管、聚氨酯保温层标准见表3
表3 介质温度≤95℃聚氨酯保温层标准表
规 格 | PE管 |
保温厚度(mm) | |||
公称直径 | PP100外径 d(mm) | PP100壁厚 t(mm) |
外径D(mm) |
厚度T(mm) | |
DN80 | 96 | 8.0 | 140 | 3 | 20 |
DN100 | 117 | 8.5 | 160 | 3 | 20 |
DN125 | 142 | 8.5 | 185 | 3 | 20 |
DN150 | 168 | 9.0 | 215 | 4 | 20 |
DN200 | 219 | 9.5 | 270 | 5 | 20 |
DN250 | 270 | 9.8 | 320 | 5 | 20 |
DN300 | 320 | 10.0 | 375 | 5 | 20 |
DN350 | 371 | 10.5 | 420 | 5 | 20 |
DN400 | 422 | 11.0 | 485 | 7 | 25 |
DN450 | 473 | 11.5 | 536 | 7 | 25 |
DN500 | 524 | 12.0 | 590 | 7 | 25 |
DN600 | 625 | 12.5 | 690 | 7 | 25 |
DN700 | 726 | 13.0 | 790 | 7 | 25 |
DN800 | 828 | 14.0 | 890 | 7 | 25 |
DN900 | 929 | 14.5 | 995 | 7 | 25 |
DN1000 | 1030 | 15.0 | 1095 | 7 | 25 |
DN1200 | 1232 | 16.0 | 1300 | 7 | 25 |
备注:1.因刚芯管本身具用隔热性能(详见刚芯管PP100与其它管材物理性能比较 表),导热系数只有0.24,所以根据计算和实测得出上述数据。 2.刚芯管隔热能力(裸管外壁温度)仅占输送介质温度的45%,故输送≤5 0℃介质无需进行外保温(除特殊要求) 3.输送介质温95℃≤介质温度≤135℃需另行计算。 4.以上数据根据管道埋设1.2米进行计算 | |||||